CVE-2026-8479 Details
Description
IEC 60870-5-104 used in bidirectional mode in RTU500 is vulnerable for a NULL pointer dereferencing, if a specially crafted sequence of messages is sent for a certain time, causing Denial of Service impact. Product is only affected if IEC 60870-5-104 functionality in bidirectional mode (BCI) is configured.
A NULL pointer dereference vulnerability has been identified in the Hitachi Energy RTU500 series, specifically within the IEC 60870-5-104 protocol when used in bidirectional mode. This vulnerability can be exploited by sending a specially crafted sequence of messages over a period of time, leading to a denial-of-service condition. The issue arises only if the IEC 60870-5-104 functionality in bidirectional mode (BCI) is configured.
Metrics
CVSS 4.0 Severity and Vector Strings:
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
Volerion
Assessed May 26, 2026CISA-ADP
Assessed May 26, 2026References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://publisher.hitachienergy.com/preview?DocumentID=8DBD000252&LanguageCode=en&DocumentPartId=&Action=Launch | [email protected] | Permission RequiredVendor |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-476 | NULL Pointer Dereference | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| Hitachi Energy RTU500 | All versions |
CPE
Remediation
| |
Change History
5 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jul 23, 2026 | CVE Translated | [email protected] |
| Jun 17, 2026 | CVE Modified | [email protected] |
| Jun 17, 2026 | CVE Modified | CISA-ADP |
| May 26, 2026 | CVE Modified | [email protected] |
| May 26, 2026 | New CVE Received | [email protected] |
Volerion