CVE-2025-9997 Details
Description
CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause command injection in BLMon that is executed in the operating system console when in a SSH session.
A command injection vulnerability has been identified in Schneider Electric's Saitel DR and Saitel DP Remote Terminal Units (RTUs). This vulnerability, categorized as OS Command Injection (CWE-78), allows for the execution of arbitrary shell commands via the BLMon Console during an SSH session. The issue is present in Saitel DR RTU versions through 11.06.29 and Saitel DP RTU versions through 11.06.33.
Users of Saitel DR RTU should upgrade to firmware version 11.06.30, while Saitel DP RTU users should upgrade to version 11.06.34. Both firmware versions include a fix for this vulnerability. After upgrading, a reboot is required to complete the process. For those who choose not to apply the update, it is recommended to restrict access to BLMon by limiting user permissions, implement firewall rules to control SSH access, and follow general cybersecurity best practices such as isolating control systems from business networks and using secure remote access methods.
Metrics
CVSS 4.0 Severity and Vector Strings:
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
Volerion
Assessed Sep 9, 2025CISA-ADP
Assessed Sep 10, 2025References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-252-02&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2025-252-02.pdf | [email protected] | AdvisoryBundleRemedyVendor |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-78 | Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| Schneider Electric Saitel DR RTU | <= 11.06.29 (semver) |
CPE
Remediation
| |
| Schneider Electric Saitel DP RTU | <= 11.06.33 (semver) |
CPE
Remediation
| |
Change History
3 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Jun 17, 2026 | CVE Modified | CISA-ADP |
| Sep 9, 2025 | New CVE Received | [email protected] |