Not a U.S. government website. NDD is an independent vulnerability database by Volerion and is not affiliated with or endorsed by NIST or NVD.
VOLERION
Volerion Security Research

NOT DEFERRED DATABASE

VULNERABILITIES

CVE-2025-9996 Details

ANALYZED


This CVE record has been analyzed and enriched by NVDAPI.com as an independent party.

Description

CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause the execution of any shell command when executing a netstat command using BLMon Console in an SSH session.

Metrics

CVSS 3.x Severity and Vector Strings:

References to Advisories, Solutions, and Tools

By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.

Weakness Enumeration

CWE-IDCWE NameSource
CWE-78Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')[email protected]

Affected Products

ProductVersions
Schneider Electric Saitel DR RTU
<= 11.06.29 (semver)

CPE

  • cpe:2.3:h:schneider-electric:saitel_dr:*:*:*:*:*:*:*:*

Remediation

  • Upgrade: 11.06.30moderate efforthttps://www.se.com/ww/en/product-country-selector/?pageType=product-range&sourceId=62685

    A reboot is needed to complete the firmware upgrade.

  • Mitigation:low effort

    Restrict access to BLMon by assigning permissions only to a limited set of user roles.

  • Mitigation:low effort

    Ensure users are assigned the least privileged role that still allows them to perform their designated tasks.

  • Mitigation:low effort

    Implement firewall rules to restrict SSH connections to the device.

Schneider Electric Saitel DP RTU
<= 11.06.33 (semver)

CPE

  • cpe:2.3:h:schneider-electric:saitel_dp:*:*:*:*:*:*:*:*

Remediation

  • Upgrade: 11.06.34moderate efforthttps://www.se.com/ww/en/product-country-selector/?pageType=product-range&sourceId=61747

    A reboot is needed to complete the firmware upgrade.

  • Mitigation:low effort

    Restrict access to BLMon by assigning permissions only to a limited set of user roles.

  • Mitigation:low effort

    Ensure users are assigned the least privileged role that still allows them to perform their designated tasks.

  • Mitigation:low effort

    Implement firewall rules to restrict SSH connections to the device.

Change History

3 change records found show changes


QUICK INFO

CVE Dictionary Entry:
CVE-2025-9996
NVD Published Date:
Sep 9, 2025
NVD Last Modified:
Jun 17, 2026
Source:
[email protected]