CVE-2025-40944 Details
Description
A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
A denial-of-service vulnerability has been identified in multiple Siemens SIMATIC products, including ET 200AL IM 157-1 PN, ET 200MP IM 155-5 PN HF, ET 200SP IM 155-6 MF HF, ET 200SP IM 155-6 PN HA, ET 200SP IM 155-6 PN R1, ET 200SP IM 155-6 PN/2 HF, ET 200SP IM 155-6 PN/3 HF, SIMATIC PN/MF Coupler, and SIMATIC PN/PN Coupler. The vulnerability arises because these devices do not properly manage S7 protocol session disconnect requests. When a valid S7 protocol Disconnect Request is received on TCP port 102, the devices enter an incorrect session state. This flaw can be exploited to make the device unresponsive, creating a denial-of-service condition that necessitates a power cycle to restore normal functionality.
Siemens has released updates for several affected products. For products where no fix is currently available, it is recommended to restrict network access to the devices, filter port 102 to accept connections only from trusted IP addresses, and follow Siemens' operational guidelines for Industrial Security. Specific update instructions can be found on the Siemens Support website.
Metrics
CVSS 4.0 Severity and Vector Strings:
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
Volerion
Assessed Jan 13, 2026CISA-ADP
Assessed Jan 13, 2026References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://cert-portal.siemens.com/productcert/html/ssa-674753.html | [email protected] | AdvisoryBundleRemedyVendor |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-400 | Uncontrolled Resource Consumption | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| Siemens SIMATIC ET 200AL IM 157-1 PN | All versions |
CPE
Remediation
| |
| Siemens SIMATIC ET 200MP IM 155-5 PN HF | All versions |
CPE
Remediation
| |
| Siemens SIMATIC ET 200SP IM 155-6 MF HF | All versions |
CPE
Remediation
| |
| Siemens SIMATIC ET 200SP IM 155-6 PN HA | All versions |
CPE
Remediation
| |
| Siemens SIMATIC ET 200SP IM 155-6 PN R1 | All versions |
CPE
Remediation
| |
| Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF | All versions |
CPE
Remediation
| |
| Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF | All versions |
CPE
Remediation
| |
| Siemens SIMATIC PN/MF Coupler | All versions |
CPE
Remediation
| |
| Siemens SIMATIC PN/PN Coupler | All versions |
CPE
Remediation
| |
| Siemens SIPLUS ET 200MP IM 155-5 PN HF | All versions |
CPE
Remediation
| |
| Siemens SIPLUS ET 200SP IM 155-6 PN HF | All versions |
CPE
Remediation
| |
| Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL | All versions |
CPE
Remediation
| |
| Siemens SIPLUS NET PN/PN Coupler | All versions |
CPE
Remediation
| |
Change History
4 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Jun 17, 2026 | CVE Modified | CISA-ADP |
| Jun 9, 2026 | CVE Modified | [email protected] |
| Jan 13, 2026 | New CVE Received | [email protected] |
Volerion