Description

CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause Denial of Service when an authenticated malicious user sends manipulated HTTPS Content-Length header to the webserver.

Metrics

References to Advisories, Solutions, and Tools

By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.

Weakness Enumeration

CWE-IDCWE NameSource
CWE-400Uncontrolled Resource Consumption[email protected]

Affected Products

ProductVersions
Schneider Electric Modicon M241
< 5.3.12.51

CPE

  • cpe:2.3:h:schneider-electric:modicon_m241:*:*:*:*:*:*:*:*
  • cpe:2.3:h:se:modicon_m241:*:*:*:*:*:*:*:*
  • cpe:2.3:o:schneider-electric:modicon_m241_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:se:modicon_m241_firmware:*:*:*:*:*:*:*:*

Remediation

  • Upgrade: 5.3.12.51moderate efforthttps://www.se.com/ww/en/product-range/62129-modicon-m241-micro-plc/#software-and-firmware

    Use the Controller Assistant feature of EcoStruxure Automation Expert – Motion v24.1 or EcoStruxure Machine Expert v2.3 to update the M241 firmware and perform a reboot. EcoStruxure Automation Expert – Motion v24.1 and EcoStruxure Machine Expert v2.3 are available via the Schneider Electric Software Installer: https://www.se.com/ww/en/download/document/ESEMACS10_INSTALLER. Additional information is available in the Quick Start Guide, chapter “EcoStruxure Automation Expert Platform Installation”.

Schneider Electric Modicon M251
< 5.3.12.51

CPE

  • cpe:2.3:h:schneider-electric:modicon_m251:*:*:*:*:*:*:*:*
  • cpe:2.3:h:se:modicon_m251:*:*:*:*:*:*:*:*
  • cpe:2.3:o:schneider-electric:modicon_m251_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:se:modicon_m251_firmware:*:*:*:*:*:*:*:*

Remediation

  • Upgrade: 5.3.12.51moderate efforthttps://www.se.com/ww/en/product-range/62130-modicon-m251-micro-plc-with-dual-channel-comm/#software-and-firmware

    Use the Controller Assistant feature of EcoStruxure Automation Expert – Motion v24.1 or EcoStruxure Machine Expert v2.3 to update the M251 firmware and perform a reboot. EcoStruxure Automation Expert – Motion v24.1 and EcoStruxure Machine Expert v2.3 are available via the Schneider Electric Software Installer: https://www.se.com/ww/en/download/document/ESEMACS10_INSTALLER. Additional information is available in the Quick Start Guide, chapter “EcoStruxure Automation Expert Platform Installation”.

Schneider Electric Modicon M258
All versions

CPE

  • cpe:2.3:h:schneider-electric:modicon_m258:*:*:*:*:*:*:*:*
  • cpe:2.3:h:se:modicon_m258:*:*:*:*:*:*:*:*
  • cpe:2.3:o:schneider-electric:modicon_m258_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:o:se:modicon_m258_firmware:*:*:*:*:*:*:*:*

Remediation

  • No remediation found in references.
Schneider Electric Modicon LMC058
All versions

CPE

  • cpe:2.3:h:schneider-electric:modicon_lmc058:*:*:*:*:*:*:*:*
  • cpe:2.3:o:schneider-electric:modicon_lmc058_firmware:*:*:*:*:*:*:*:*

Remediation

  • No remediation found in references.
Schneider Electric Modicon M262
< 5.3.9.18

CPE

  • cpe:2.3:o:schneider-electric:modicon_m262_firmware:*:*:*:*:*:*:*:*

Remediation

  • Upgrade: 5.3.9.18moderate efforthttps://www.se.com/ww/en/product-range/65771-logic-motion-controller-modicon-m262/#software-and-firmware

    Use the Controller Assistant feature of EcoStruxure Automation Expert – Motion v24.1 or EcoStruxure Machine Expert v2.3 to update the M262 firmware and perform a reboot. EcoStruxure Automation Expert – Motion v24.1 and EcoStruxure Machine Expert v2.3 are available via the Schneider Electric Software Installer: https://www.se.com/ww/en/download/document/ESEMACS10_INSTALLER. Additional information is available in the Quick Start Guide, chapter “EcoStruxure Automation Expert Platform Installation”.