CVE-2025-29931 Details
Description
A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2). The affected product does not properly validate a length field in a serialized message which it uses to determine the amount of memory to be allocated for deserialization. This could allow an unauthenticated remote attacker to cause the application to allocate exhaustive amounts of memory and subsequently create a partial denial of service condition. Successful exploitation is only possible in redundant Telecontrol Server Basic setups and only if the connection between the redundant servers has been disrupted.
A denial-of-service vulnerability has been identified in Siemens TeleControl Server Basic, all versions prior to V3.1.2.2. The issue arises because the application fails to properly validate a length field in serialized messages, which is used to determine how much memory should be allocated for deserialization. This flaw could enable an unauthenticated remote attacker to cause excessive memory allocation, creating a partial denial-of-service condition. Successful exploitation is possible only in redundant TeleControl Server Basic setups, and only if the connection between the redundant servers has been disrupted.
Users are advised to update Siemens TeleControl Server Basic to version V3.1.2.2 or later. If redundancy is not needed, Telecontrol Server Basic redundancy can be disabled to mitigate the risk.
Metrics
CVSS 4.0 Severity and Vector Strings:
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
CISA-ADP
Assessed Apr 17, 2025References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://cert-portal.siemens.com/productcert/html/ssa-395348.html | [email protected] | Vendor Advisory |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-130 | Improper Handling of Length Parameter Inconsistency | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| siemens telecontrol server basic | < 3.1.2.2 |
CPE
Remediation
| |
Change History
4 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Jun 17, 2026 | CVE Modified | CISA-ADP |
| Aug 19, 2025 | Initial Analysis | [email protected] |
| Apr 17, 2025 | New CVE Received | [email protected] |