Not a U.S. government website. NDD is an independent vulnerability database by Volerion and is not affiliated with or endorsed by NIST or NVD.
VOLERION
Volerion Security Research

NOT DEFERRED DATABASE

VULNERABILITIES

CVE-2025-13824 Details

ANALYZED


This CVE record has been analyzed and enriched by NVDAPI.com as an independent party.

Description

A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.

Metrics

CVSS 3.x Severity and Vector Strings:

References to Advisories, Solutions, and Tools

By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.

Weakness Enumeration

CWE-IDCWE NameSource
CWE-763Release of Invalid Pointer or Reference[email protected]

Affected Products

ProductVersions
Rockwell Automation Micro820
<= V14.011

CPE

  • cpe:2.3:h:rockwellautomation:micro820:*:*:*:*:*:*:*:*
  • cpe:2.3:o:rockwellautomation:micro820_firmware:*:*:*:*:*:*:*:*
Rockwell Automation Micro850
<= V23.011
<= V12.013

CPE

  • cpe:2.3:h:rockwellautomation:micro850:*:*:*:*:*:*:*:*
  • cpe:2.3:o:rockwellautomation:micro850_firmware:*:*:*:*:*:*:*:*
Rockwell Automation Micro870
<= V23.011
<= V12.013

CPE

  • cpe:2.3:o:rockwellautomation:micro870_firmware:*:*:*:*:*:*:*:*
  • cpe:2.3:h:rockwellautomation:micro870:*:*:*:*:*:*:*:*

Change History

5 change records found show changes


QUICK INFO

CVE Dictionary Entry:
CVE-2025-13824
NVD Published Date:
Dec 15, 2025
NVD Last Modified:
Sep 3, 2026
Source:
[email protected]
CVE-2025-13824 Details - Not Deferred