CVE-2025-13824 Details
Description
A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault.
A vulnerability exists in Rockwell Automation's Micro820, Micro850, and Micro870 controllers due to improper handling of malformed Common Industrial Protocol (CIP) packets. This issue was identified during internal testing and can cause the controller to enter a hard fault, indicated by a solid red Fault LED, rendering it unresponsive. After a power cycle, the controller transitions to a recoverable fault state, with the MS LED and Fault LED flashing red, and reports fault code 0xF019. To recover, the fault must be cleared.
Users can upgrade to Micro850/870 controllers (L50E/L70E) version 23.012. For Micro820 (LC20) controllers, version 23.011 is available. Instructions for downloading the updated firmware can be found on the Rockwell Automation Compatibility Center website.
Metrics
CVSS 4.0 Severity and Vector Strings:
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
Volerion
Assessed Dec 15, 2025CISA-ADP
Assessed Dec 15, 2025References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1766.html | [email protected] | AdvisoryBundleRemedyVendor |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-763 | Release of Invalid Pointer or Reference | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| Rockwell Automation Micro820 | <= V14.011 |
CPE
Remediation
| |
| Rockwell Automation Micro850 | <= V23.011 <= V12.013 |
CPE
Remediation
| |
| Rockwell Automation Micro870 | <= V23.011 <= V12.013 |
CPE
Remediation
| |
Change History
5 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Sep 3, 2026 | CVE Modified | [email protected] |
| Sep 3, 2026 | CVE Modified | CISA-ADP |
| Jun 17, 2026 | CVE Modified | [email protected] |
| Jun 17, 2026 | CVE Modified | CISA-ADP |
| Dec 15, 2025 | New CVE Received | [email protected] |