Description

FINS (Factory Interface Network Service) is a message communication protocol, which is designed to be used in closed FA (Factory Automation) networks, and is used in FA networks composed of OMRON products. Multiple OMRON products that implement FINS protocol contain following security issues -- (1)Plaintext communication, and (2)No authentication required. When FINS messages are intercepted, the contents may be retrieved. When arbitrary FINS messages are injected, any commands may be executed on, or the system information may be retrieved from, the affected device. Affected products and versions are as follows: SYSMAC CS-series CPU Units, all versions, SYSMAC CJ-series CPU Units, all versions, SYSMAC CP-series CPU Units, all versions, SYSMAC NJ-series CPU Units, all versions, SYSMAC NX1P-series CPU Units, all versions, SYSMAC NX102-series CPU Units, all versions, and SYSMAC NX7 Database Connection CPU Units (Ver.1.16 or later)

Metrics

References to Advisories, Solutions, and Tools

By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.

Weakness Enumeration

CWE-IDCWE NameSource
CWE-306Missing Authentication for Critical Function[email protected]
CWE-306Missing Authentication for Critical FunctionCISA-ADP

Affected Products

ProductVersions

Change History