CVE-2023-2071 Details
Description
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
Metrics
CVSS 4.0 Severity and Vector Strings:
No CVSS 4.0 data is available for this CVE.
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
CISA-ADP
Assessed Sep 25, 2024References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724 | CVE | Vendor Advisory |
| https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724 | [email protected] | Vendor Advisory |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-434 | Unrestricted Upload of File with Dangerous Type | [email protected] |
| CWE-20 | Improper Input Validation | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| rockwellautomation factorytalk view | <= 13.0 |
CPE
Remediation
| |
| rockwellautomation panelview plus | All versions |
CPE
Remediation
| |
Change History
5 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Jun 17, 2026 | CVE Modified | CISA-ADP |
| Nov 21, 2024 | CVE Modified | CVE |
| May 14, 2024 | CVE Modified | [email protected] |
| Sep 14, 2023 | Initial Analysis | [email protected] |