Not a U.S. government website. NDD is an independent vulnerability database by Volerion and is not affiliated with or endorsed by NIST or NVD.
CVE-2022-4608 Details
Description
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
Metrics
CVSS 4.0 Severity and Vector Strings:
No CVSS 4.0 data is available for this CVE.
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
CISA-ADP
Assessed Mar 5, 2025Exploitation: NoneAutomatable: YesTechnical Impact: Partial
References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-787 | Out-of-bounds Write | [email protected] |
| CWE-787 | Out-of-bounds Write | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| hitachienergy rtu500 firmware | 13.3.1 13.3.2 13.3.3 13.4.1 |
CPE
Remediation
| |
| hitachienergy rtu500 | All versions |
CPE
Remediation
| |
Change History
6 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Jun 17, 2026 | CVE Modified | CISA-ADP |
| Nov 21, 2024 | CVE Modified | CVE |
| Sep 25, 2024 | CVE Modified | [email protected] |
| May 14, 2024 | CVE Modified | [email protected] |
| Aug 3, 2023 | Initial Analysis | [email protected] |