CVE-2022-30320 Details
Description
Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a Saia Burgess Controls (SBC) PCD S-Bus weak credential hashing scheme issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication is done by using the S-Bus 'write byte' message to a specific address and supplying a hashed version of the password. The hashing algorithm used is based on CRC-16 and as such not cryptographically secure. An insecure hashing algorithm is used. An attacker capable of passively observing traffic can intercept the hashed credentials and trivially find collisions allowing for authentication without having to bruteforce a keyspace defined by the actual strength of the password. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Metrics
CVSS 4.0 Severity and Vector Strings:
No CVSS 4.0 data is available for this CVE.
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
No SSVC data is available for this CVE.
References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03 | CVE | Third Party AdvisoryUS Government Resource |
| https://www.forescout.com/blog/ | CVE | Not ApplicableThird Party Advisory |
| https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03 | [email protected] | Third Party AdvisoryUS Government Resource |
| https://www.forescout.com/blog/ | [email protected] | Not ApplicableThird Party Advisory |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-327 | Use of a Broken or Risky Cryptographic Algorithm | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| honeywell saia pg5 controls suite | All versions |
CPE
Remediation
| |
Change History
5 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Nov 21, 2024 | CVE Modified | CVE |
| May 14, 2024 | CVE Modified | [email protected] |
| Feb 14, 2024 | Reanalysis | [email protected] |
| Aug 10, 2022 | Initial Analysis | [email protected] |