CVE-2022-2502 Details
Description
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
Metrics
CVSS 4.0 Severity and Vector Strings:
No CVSS 4.0 data is available for this CVE.
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
CISA-ADP
Assessed Mar 5, 2025References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-20 | Improper Input Validation | [email protected] |
| CWE-20 | Improper Input Validation | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| hitachienergy rtu500 firmware | 13.3.1 13.3.2 13.3.3 13.4.1 |
CPE
Remediation
| |
| hitachienergy rtu500 | All versions |
CPE
Remediation
| |
Change History
6 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Jun 17, 2026 | CVE Modified | CISA-ADP |
| Nov 21, 2024 | CVE Modified | CVE |
| Sep 25, 2024 | CVE Modified | [email protected] |
| May 14, 2024 | CVE Modified | [email protected] |
| Aug 3, 2023 | Initial Analysis | [email protected] |