CVE-2021-37206 Details
Description
A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP100 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP300 (All versions < V8.80). Received webpackets are not properly processed. An unauthenticated remote attacker with access to any of the Ethernet interfaces could send specially crafted packets to force a restart of the target device.
A denial-of-service vulnerability has been identified in Siemens SIPROTEC 5 relays with CPU variants CP050, CP100, and CP300, all running versions prior to V8.80. The issue arises because received webpackets are not properly processed, allowing an unauthenticated remote attacker with access to any Ethernet interface to send specially crafted packets that force the target device to restart.
Siemens has released a patch for this vulnerability. Users are advised to update to version V8.80 or later. For guidance on applying the update, refer to the Siemens support page for SIPROTEC 5.
Metrics
CVSS 4.0 Severity and Vector Strings:
No CVSS 4.0 data is available for this CVE.
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
No SSVC data is available for this CVE.
References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://cert-portal.siemens.com/productcert/pdf/ssa-500748.pdf | CVE | PatchVendor Advisory |
| https://cert-portal.siemens.com/productcert/pdf/ssa-500748.pdf | [email protected] | PatchVendor Advisory |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-20 | Improper Input Validation | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| siemens siprotec 5 with cpu variant cp050 | < 8.80 |
CPE
Remediation
| |
| siemens siprotec 5 with cpu variant cp100 | < 8.80 |
CPE
Remediation
| |
| siemens siprotec 5 with cpu variant cp300 | < 8.80 |
CPE
Remediation
| |
Change History
6 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Nov 21, 2024 | CVE Modified | CVE |
| May 14, 2024 | CVE Modified | [email protected] |
| Dec 14, 2021 | Modified Analysis | [email protected] |
| Oct 12, 2021 | CVE Modified | [email protected] |
| Sep 28, 2021 | Initial Analysis | [email protected] |