CVE-2019-5171 Details
Description
An exploitable command injection vulnerability exists in the iocheckd service ‘I/O-Check’ function of the WAGO PFC 200 Firmware version 03.02.02(14). An attacker can send specially crafted packet at 0x1ea48 to the extracted hostname value from the xml file that is used as an argument to /etc/config-tools/config_interfaces interface=X1 state=enabled ip-address=<contents of ip node> using sprintf().
Metrics
CVSS 4.0 Severity and Vector Strings:
No CVSS 4.0 data is available for this CVE.
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
No SSVC data is available for this CVE.
References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://talosintelligence.com/vulnerability_reports/TALOS-2019-0962 | CVE | ExploitTechnical DescriptionThird Party Advisory |
| https://talosintelligence.com/vulnerability_reports/TALOS-2019-0962 | [email protected] | ExploitTechnical DescriptionThird Party Advisory |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-78 | Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| wago pfc200 firmware | 03.02.02(14) |
CPE
Remediation
| |
| wago pfc200 | All versions |
CPE
Remediation
| |
Change History
4 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Nov 21, 2024 | CVE Modified | CVE |
| May 14, 2024 | CVE Modified | [email protected] |
| Mar 17, 2020 | Initial Analysis | [email protected] |