CVE-2019-10935 Details
Description
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd 11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC Professional (TIA Portal V13) (All versions), SIMATIC WinCC Professional (TIA Portal V14) (All versions < V14 SP1 Upd 9), SIMATIC WinCC Professional (TIA Portal V15) (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). The SIMATIC WinCC DataMonitor web application of the affected products allows to upload arbitrary ASPX code. The security vulnerability could be exploited by an authenticated attacker with network access to the WinCC DataMonitor application. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.
Metrics
CVSS 4.0 Severity and Vector Strings:
No CVSS 4.0 data is available for this CVE.
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
No SSVC data is available for this CVE.
References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://cert-portal.siemens.com/productcert/pdf/ssa-121293.pdf | CVE | PatchVendor Advisory |
| https://cert-portal.siemens.com/productcert/pdf/ssa-121293.pdf | [email protected] | PatchVendor Advisory |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| CWE-434 | Unrestricted Upload of File with Dangerous Type | [email protected] |
| CWE-434 | Unrestricted Upload of File with Dangerous Type | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| siemens simatic pcs 7 | 8.0 8.1 8.2 9.0 |
CPE
Remediation
| |
| siemens simatic wincc | <= 7.2 7.3 - 7.3 update_1 7.3 update_10 7.3 update_11 7.3 update_13 7.3 update_4 7.4 - 7.4 sp1 7.4 update_1 7.5 13 - 13 sp2 14 14 - 14 sp1 15 |
CPE
Remediation
| |
| siemens simatic wincc runtime | 13 13 - 13 sp1 13 sp2 14 - 14 sp1 15 - 15 update_4 15.1 - 15.1 update_1 |
CPE
Remediation
| |
Change History
11 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Nov 21, 2024 | CVE Modified | CVE |
| May 14, 2024 | CVE Modified | [email protected] |
| Oct 10, 2019 | CVE Modified | [email protected] |
| Oct 9, 2019 | CVE Modified | [email protected] |
| Sep 13, 2019 | CVE Modified | [email protected] |
| Aug 13, 2019 | CVE Modified | [email protected] |
| Aug 13, 2019 | CVE Modified | [email protected] |
| Jul 19, 2019 | Initial Analysis | [email protected] |
| Jul 15, 2019 | CVE Modified | [email protected] |
| Jul 12, 2019 | CVE Modified | [email protected] |