CVE-2018-4858 Details
Description
A vulnerability has been identified in IEC 61850 system configurator (All versions < V5.80), DIGSI 5 (affected as IEC 61850 system configurator is incorporated) (All versions < V7.80), DIGSI 4 (All versions < V4.93), SICAM PAS/PQS (All versions < V8.11), SICAM PQ Analyzer (All versions < V3.11), SICAM SCC (All versions < V9.02 HF3). A service of the affected products listening on all of the host's network interfaces on either port 4884/TCP, 5885/TCP, or port 5886/TCP could allow an attacker to either exfiltrate limited data from the system or to execute code with Microsoft Windows user permissions. Successful exploitation requires an attacker to be able to send a specially crafted network request to the vulnerable service and a user interacting with the service's client application on the host. In order to execute arbitrary code with Microsoft Windows user permissions, an attacker must be able to plant the code in advance on the host by other means. The vulnerability has limited impact to confidentiality and integrity of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
Metrics
CVSS 4.0 Severity and Vector Strings:
No CVSS 4.0 data is available for this CVE.
CVSS 3.x Severity and Vector Strings:
No data available for CVSS Version 2.0 on this CVE.
No SSVC data is available for this CVE.
References to Advisories, Solutions, and Tools
By selecting these links, you will be leaving this site. These are references gathered from the official CVE record and are not endorsed by Volerion.
| URL | Source(s) | Tag(s) |
|---|---|---|
| https://cert-portal.siemens.com/productcert/pdf/ssa-159860.pdf | CVE | Vendor Advisory |
| https://ics-cert.us-cert.gov/advisories/ICSA-18-317-01 | CVE | Third Party AdvisoryUS Government Resource |
| http://www.securityfocus.com/bid/105933 | CVE | Third Party AdvisoryVDB Entry |
| https://cert-portal.siemens.com/productcert/pdf/ssa-159860.pdf | [email protected] | Vendor Advisory |
| https://ics-cert.us-cert.gov/advisories/ICSA-18-317-01 | [email protected] | Third Party AdvisoryUS Government Resource |
| http://www.securityfocus.com/bid/105933 | [email protected] | Third Party AdvisoryVDB Entry |
Weakness Enumeration
| CWE-ID | CWE Name | Source |
|---|---|---|
| NVD-CWE-noinfo | Insufficient Information to Classify Weakness | [email protected] |
| CWE-284 | Improper Access Control | [email protected] |
Affected Products
| Product | Versions |
|---|---|
| siemens ec 61850 system configurator firmware | < 5.80 |
CPE
Remediation
| |
| siemens ec 61850 system configurator | All versions |
CPE
Remediation
| |
| siemens sicam pq analyzer firmware | < 3.11 |
CPE
Remediation
| |
| siemens sicam pq analyzer | All versions |
CPE
Remediation
| |
| siemens sicam scc firmware | All versions |
CPE
Remediation
| |
| siemens sicam scc | All versions |
CPE
Remediation
| |
| siemens digsi 4 firmware | All versions |
CPE
Remediation
| |
| siemens digsi 4 | All versions |
CPE
Remediation
| |
| siemens digsi 5 firmware | < 7.80 |
CPE
Remediation
| |
| siemens digsi 5 | All versions |
CPE
Remediation
| |
| siemens sicam pas/pqs | < 8.11 |
CPE
Remediation
| |
Change History
12 change records found show changes
| Date | Action | Recorded By |
|---|---|---|
| Jun 17, 2026 | CVE Modified | [email protected] |
| Nov 21, 2024 | CVE Modified | CVE |
| May 14, 2024 | CVE Modified | [email protected] |
| Oct 16, 2023 | Modified Analysis | [email protected] |
| Oct 13, 2023 | CPE Deprecation Remap | [email protected] |
| Oct 13, 2023 | CPE Deprecation Remap | [email protected] |
| Oct 9, 2019 | CVE Modified | [email protected] |
| Oct 3, 2019 | CWE Remap | [email protected] |
| Dec 13, 2018 | CVE Modified | [email protected] |
| Nov 16, 2018 | CVE Modified | [email protected] |
| Nov 14, 2018 | CVE Modified | [email protected] |
| Sep 14, 2018 | Initial Analysis | [email protected] |